Vulnerabilities (CVE)

Filtered by vendor Schneider-electric Subscribe
Total 768 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2017-5157 2 Schneider-electric, Schneider Electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2026-06-17 4.3 MEDIUM 6.1 MEDIUM
An issue was discovered in Schneider Electric homeLYnk Controller, LSS100100, all versions prior to V1.5.0. The homeLYnk controller is susceptible to a cross-site scripting attack. User inputs can be manipulated to cause execution of JavaScript code.
CVE-2017-5155 1 Schneider-electric 1 Wonderware Historian 2026-06-17 7.5 HIGH 7.3 HIGH
An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well.
CVE-2017-14024 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2026-06-17 10.0 HIGH 9.8 CRITICAL
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.
CVE-2017-13997 1 Schneider-electric 2 Wonderware Indusoft Web Studio, Wonderware Intouch 2026-06-17 10.0 HIGH 9.8 CRITICAL
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
CVE-2016-8374 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2026-06-17 7.8 HIGH 7.5 HIGH
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker may be able to disrupt a targeted web server, resulting in a denial of service because of UNCONTROLLED RESOURCE CONSUMPTION.
CVE-2016-8367 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2026-06-17 5.0 MEDIUM 5.3 MEDIUM
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack.
CVE-2016-8354 1 Schneider-electric 1 Unity Pro 2026-06-17 5.1 MEDIUM 7.0 HIGH
An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions.
CVE-2016-8352 1 Schneider-electric 6 Connexium Firmware, Tcsefec23f3f20, Tcsefec23f3f21 and 3 more 2026-06-17 7.5 HIGH 10.0 CRITICAL
An issue was discovered in Schneider Electric ConneXium firewalls TCSEFEC23F3F20 all versions, TCSEFEC23F3F21 all versions, TCSEFEC23FCF20 all versions, TCSEFEC23FCF21 all versions, and TCSEFEC2CF3F20 all versions. A stack-based buffer overflow can be triggered during the SNMP login authentication process that may allow an attacker to remotely execute code.
CVE-2016-5818 1 Schneider-electric 2 Powerlogic Pm8ecc, Powerlogic Pm8ecc Firmware 2026-06-17 7.5 HIGH 9.8 CRITICAL
An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device.
CVE-2016-5815 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2026-06-17 7.5 HIGH 9.8 CRITICAL
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes.
CVE-2016-5809 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2026-06-17 6.8 MEDIUM 8.8 HIGH
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved.
CVE-2016-4529 1 Schneider-electric 3 M171, M172, Somachine Hvac Firmware 2026-06-17 7.5 HIGH 7.3 HIGH
An unspecified ActiveX control in Schneider Electric SoMachine HVAC Programming Software for M171/M172 Controllers before 2.1.0 allows remote attackers to execute arbitrary code via unknown vectors, related to the INTERFACESAFE_FOR_UNTRUSTED_CALLER (aka safe for scripting) flag.
CVE-2016-4520 1 Schneider-electric 1 Pelco Digital Sentry Video Management System Firmware 2026-06-17 10.0 HIGH 9.8 CRITICAL
Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors.
CVE-2016-4513 1 Schneider-electric 2 Powerlogic Pm8ecc, Powerlogic Pm8ecc Firmware 2026-06-17 4.3 MEDIUM 6.1 MEDIUM
Cross-site scripting (XSS) vulnerability in the Schneider Electric PowerLogic PM8ECC module before 2.651 for PowerMeter 800 devices allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2016-2292 1 Schneider-electric 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more 2026-06-17 4.3 MEDIUM 6.5 MEDIUM
Stack-based buffer overflow in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allows remote attackers to execute arbitrary code via unspecified vectors.
CVE-2016-2291 1 Schneider-electric 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more 2026-06-17 4.3 MEDIUM 6.5 MEDIUM
Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allow remote attackers to execute arbitrary code or cause a denial of service (out-of-bounds read) via unspecified vectors.
CVE-2016-2290 1 Schneider-electric 4 Proface Gp-pro Ex Ex-ed, Proface Gp-pro Ex Pfxexedls, Proface Gp-pro Ex Pfxexedv and 1 more 2026-06-17 6.8 MEDIUM 8.8 HIGH
Heap-based buffer overflow in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 allows remote attackers to execute arbitrary code via unspecified vectors.
CVE-2016-2278 1 Schneider-electric 4 Struxureware Building Operations Automation Server As, Struxureware Building Operations Automation Server As-p, Struxureware Building Operations Automation Server As-p Firmware and 1 more 2026-06-17 9.0 HIGH 7.2 HIGH
Schneider Electric Struxureware Building Operations Automation Server AS 1.7 and earlier and AS-P 1.7 and earlier allows remote authenticated administrators to execute arbitrary OS commands by defeating an msh (aka Minimal Shell) protection mechanism.
CVE-2015-8561 1 Schneider-electric 1 Proclima 2026-06-17 6.8 MEDIUM N/A
The F1BookView ActiveX control in F1 Bookview in Schneider Electric ProClima before 6.2 allows remote attackers to execute arbitrary code or cause a denial of service (memory corruption) via a crafted integer value to the (1) AttachToSS, (2) CopyAll, (3) CopyRange, (4) CopyRangeEx, or (5) SwapTable method, a different vulnerability than CVE-2015-7918.
CVE-2015-7937 1 Schneider-electric 13 Bmxnoc0401, Bmxnoe0100, Bmxnoe0100h and 10 more 2026-06-17 10.0 HIGH N/A
Stack-based buffer overflow in the GoAhead Web Server on Schneider Electric Modicon M340 PLC BMXNOx and BMXPx devices allows remote attackers to execute arbitrary code via a long password in HTTP Basic Authentication data.