Vulnerabilities (CVE)

Filtered by vendor Schneider-electric Subscribe
Total 758 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2017-7971 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 4.0 MEDIUM 6.5 MEDIUM
A vulnerability exists in Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 that allows the use of outdated cipher suites and improper verification of peer SSL Certificate.
CVE-2016-5818 1 Schneider-electric 2 Powerlogic Pm8ecc, Powerlogic Pm8ecc Firmware 2025-04-20 7.5 HIGH 9.8 CRITICAL
An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device.
CVE-2017-9961 1 Schneider-electric 1 Pro-face Gp Pro Ex 2025-04-20 4.6 MEDIUM 7.8 HIGH
A vulnerability exists in Schneider Electric's Pro-Face GP Pro EX version 4.07.000 that allows an attacker to execute arbitrary code. Malicious code installation requires an access to the computer. By placing a specific DLL/OCX file, an attacker is able to force the process to load arbitrary DLL and execute arbitrary code in the context of the process.
CVE-2017-7965 1 Schneider-electric 1 Somachine Hvac 2025-04-20 4.6 MEDIUM 7.3 HIGH
A buffer overflow vulnerability exists in Programming Software executable AlTracePrint.exe, in Schneider Electric's SoMachine HVAC v2.1.0 for Modicon M171/M172 Controller.
CVE-2017-6017 1 Schneider-electric 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more 2025-04-20 7.8 HIGH 7.5 HIGH
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
CVE-2017-5157 2 Schneider-electric, Schneider Electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2025-04-20 4.3 MEDIUM 6.1 MEDIUM
An issue was discovered in Schneider Electric homeLYnk Controller, LSS100100, all versions prior to V1.5.0. The homeLYnk controller is susceptible to a cross-site scripting attack. User inputs can be manipulated to cause execution of JavaScript code.
CVE-2017-9957 1 Schneider-electric 1 U.motion Builder 2025-04-20 7.5 HIGH 9.8 CRITICAL
A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the web service contains a hidden system account with a hardcoded password. An attacker can use this information to log into the system with high-privilege credentials.
CVE-2016-8374 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2025-04-20 7.8 HIGH 7.5 HIGH
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker may be able to disrupt a targeted web server, resulting in a denial of service because of UNCONTROLLED RESOURCE CONSUMPTION.
CVE-2017-7967 1 Schneider-electric 1 Vampset 2025-04-20 2.1 LOW 5.5 MEDIUM
All versions of VAMPSET software produced by Schneider Electric, prior to V2.2.189, are susceptible to a memory corruption vulnerability when a corrupted vf2 file is used. This vulnerability causes the software to halt or not start when trying to open the corrupted file. This vulnerability occurs when fill settings are intentionally malformed and is opened in a standalone state, without connection to a protection relay. This attack is not considered to be remotely exploitable. This vulnerability has no effect on the operation of the protection relay to which VAMPSET is connected. As Windows operating system remains operational and VAMPSET responds, it is able to be shut down through its normal closing protocol.
CVE-2017-6033 1 Schneider-electric 1 Interactive Graphical Scada System 2025-04-20 6.8 MEDIUM 7.8 HIGH
A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path.
CVE-2017-9629 1 Schneider-electric 1 Wonderware Archestra Logger 2025-04-20 10.0 HIGH 9.8 CRITICAL
A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context of a highly privileged account.
CVE-2017-7966 1 Schneider-electric 1 Somachine 2025-04-20 6.8 MEDIUM 8.8 HIGH
A DLL Hijacking vulnerability in the programming software in Schneider Electric's SoMachine HVAC v2.1.0 allows a remote attacker to execute arbitrary code on the targeted system. The vulnerability exists due to the improper loading of a DLL.
CVE-2016-8367 1 Schneider-electric 16 Magelis Gto Advanced Optimum Panel, Magelis Gto Advanced Optimum Panel Firmware, Magelis Gtu Universal Panel and 13 more 2025-04-20 5.0 MEDIUM 5.3 MEDIUM
An issue was discovered in Schneider Electric Magelis HMI Magelis GTO Advanced Optimum Panels, all versions, Magelis GTU Universal Panel, all versions, Magelis STO5xx and STU Small panels, all versions, Magelis XBT GH Advanced Hand-held Panels, all versions, Magelis XBT GK Advanced Touchscreen Panels with Keyboard, all versions, Magelis XBT GT Advanced Touchscreen Panels, all versions, and Magelis XBT GTW Advanced Open Touchscreen Panels (Windows XPe). An attacker can open multiple connections to a targeted web server and keep connections open preventing new connections from being made, rendering the web server unavailable during an attack.
CVE-2017-5155 1 Schneider-electric 1 Wonderware Historian 2025-04-20 7.5 HIGH 7.3 HIGH
An issue was discovered in Schneider Electric Wonderware Historian 2014 R2 SP1 P01 and earlier. Wonderware Historian creates logins with default passwords, which can allow a malicious entity to compromise Historian databases. In some installation scenarios, resources beyond those created by Wonderware Historian may be compromised as well.
CVE-2017-7689 1 Schneider-electric 2 Homelynk Controller Lss100100, Homelynk Controller Lss100100 Firmware 2025-04-20 10.0 HIGH 9.8 CRITICAL
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0.
CVE-2017-6028 1 Schneider-electric 4 Modicon M241, Modicon M241 Firmware, Modicon M251 and 1 more 2025-04-20 5.0 MEDIUM 9.8 CRITICAL
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
CVE-2017-6032 1 Schneider-electric 2 Modbus, Modbus Firmware 2025-04-20 5.0 MEDIUM 5.3 MEDIUM
A Violation of Secure Design Principles issue was discovered in Schneider Electric Modicon Modbus Protocol. The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks.
CVE-2017-7969 1 Schneider-electric 3 Citect Anywhere, Powerscada Anywhere, Powerscada Expert 2025-04-20 6.8 MEDIUM 8.8 HIGH
A cross-site request forgery vulnerability exists on the Secure Gateway component of Schneider Electric's PowerSCADA Anywhere v1.0 redistributed with PowerSCADA Expert v8.1 and PowerSCADA Expert v8.2 and Citect Anywhere version 1.0 for multiple state-changing requests. This type of attack requires some level of social engineering in order to get a legitimate user to click on or access a malicious link/site containing the CSRF attack.
CVE-2016-5809 1 Schneider-electric 6 Ion5000, Ion7300, Ion7500 and 3 more 2025-04-20 6.8 MEDIUM 8.8 HIGH
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved.
CVE-2017-9958 1 Schneider-electric 1 U.motion Builder 2025-04-20 7.2 HIGH 7.8 HIGH
An improper access control vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an improper handling of the system configuration can allow an attacker to execute arbitrary code under the context of root.