Search Results (823 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2026-2405 1 Schneider-electric 1 Powerchute Serial Shutdown 2026-04-22 6.5 Medium
CWE-400 Uncontrolled Resource Consumption vulnerability exists that could cause excessive troubleshooting zip file creation and denial of service when a Web Admin user floods the system with POST /helpabout requests.
CVE-2026-1227 1 Schneider-electric 2 Ecostruxure Building Operation Webstation, Ecostruxure Building Operation Workstation 2026-04-17 N/A
CWE-611: Improper Restriction of XML External Entity Reference vulnerability exists that could cause unauthorized disclosure of local files, interaction within the EBO system, or denial of service conditions when a local user uploads a specially crafted TGML graphics file to the EBO server from Workstation.
CVE-2026-1226 1 Schneider-electric 2 Ecostruxure Building Operation Webstation, Ecostruxure Building Operation Workstation 2026-04-17 N/A
CWE‑94: Improper Control of Generation of Code vulnerability exists that could cause execution of untrusted or unintended code within the application when maliciously crafted design content is processed through a TGML graphics file.
CVE-2026-4832 1 Schneider-electric 25 Easergy P14x, Easergy P24x, Easergy P341 and 22 more 2026-04-17 N/A
CWE-798 Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to sensitive device information when an unauthenticated attacker is able to interrogate the SNMP port.
CVE-2026-1286 1 Schneider-electric 2 Ecostruxure Foxboro Dcs Control Software, Foxboro Dcs 2026-04-17 6.5 Medium
CWE-502: Deserialization of untrusted data vulnerability exists that could lead to loss of confidentiality, integrity and potential remote code execution on workstation when an admin authenticated user opens a malicious project file.
CVE-2026-2273 1 Schneider-electric 1 Ecostruxure Automation Expert 2026-04-17 8.2 High
CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exist that could cause execution of untrusted commands on the engineering workstation which could result in a limited compromise of the workstation and a potential loss of Confidentiality, Integrity and Availability of the subsequent system when an authenticated user opens a malicious project file.
CVE-2025-11566 1 Schneider-electric 1 Powerchute Serial Shutdown 2026-04-15 N/A
CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that would allow an attacker on the local network to gain access to the user account by performing an arbitrary number of authentication attempts with different credentials on the /REST/shutdownnow endpoint.
CVE-2025-54926 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 7.2 High
CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause remote code execution when an authenticated attacker with admin privileges uploads a malicious file over HTTP which then gets executed.
CVE-2025-6625 1 Schneider-electric 12 Bmxngd0100, Bmxngd0100 Firmware, Bmxnoc0401 and 9 more 2026-04-15 7.5 High
CWE-20: Improper Input Validation vulnerability exists that could cause a Denial Of Service when specific crafted FTP command is sent to the device.
CVE-2025-8448 1 Schneider-electric 2 Ecostruxure Building Operation Enterprise Server, Ecostruxure Workstation 2026-04-15 N/A
CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause unauthorized access to sensitive credential data when an attacker is able to capture local SMB traffic between a valid user within the BMS network and the vulnerable products.
CVE-2024-8938 1 Schneider-electric 3 Modicon M340, Modicon Mc80, Modicon Momentum Unity M1e Processor 2026-04-15 8.1 High
CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a potential arbitrary code execution after a successful Man-In-The-Middle attack followed by sending a crafted Modbus function call to tamper with memory area involved in memory size computation.
CVE-2024-9002 1 Schneider-electric 1 Easergy Studio 2026-04-15 7.8 High
CWE-269: Improper Privilege Management vulnerability exists that could cause unauthorized access, loss of confidentiality, integrity, and availability of the workstation when non-admin authenticated user tries to perform privilege escalation by tampering with the binaries
CVE-2025-11565 1 Schneider-electric 1 Powerchute Serial Shutdown 2026-04-15 N/A
CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause elevated system access when a Web Admin user on the local network tampers with the POST /REST/UpdateJRE request payload.
CVE-2024-8935 1 Schneider-electric 3 Modicon M340 Bmxp341000, Modicon Mc80 Bmkc8020301, Modicon Momentum Unity M1e Processor 2026-04-15 7.5 High
CWE-290: Authentication Bypass by Spoofing vulnerability exists that could cause a denial of service and loss of confidentiality and integrity of controllers when conducting a Man-In-The-Middle attack between the controller and the engineering workstation while a valid user is establishing a communication session. This vulnerability is inherent to Diffie Hellman algorithm which does not protect against Man-In-The-Middle attacks.
CVE-2024-8936 1 Schneider-electric 1 Modicon M340 2026-04-15 6.5 Medium
CWE-20: Improper Input Validation vulnerability exists that could lead to loss of confidentiality of controller memory after a successful Man-In-The-Middle attack followed by sending a crafted Modbus function call used to tamper with memory.
CVE-2025-11567 1 Schneider-electric 1 Powerchute Serial Shutdown 2026-04-15 N/A
CWE-276: Incorrect Default Permissions vulnerability exists that could cause elevated system access when the target installation folder is not properly secured.
CVE-2025-54924 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 7.5 High
CWE-918: Server-Side Request Forgery (SSRF) vulnerability exists that could cause unauthorized access to sensitive data when an attacker sends a specially crafted document to a vulnerable endpoint.
CVE-2025-54925 1 Schneider-electric 2 Ecostruxure Power Monitoring Expert, Ecostruxure Power Operation With Advanced Reports 2026-04-15 7.5 High
CWE-918: Server-Side Request Forgery (SSRF) vulnerability exists that could cause unauthorized access to sensitive data when an attacker configures the application to access a malicious url.
CVE-2024-6918 1 Schneider-electric 1 Accutech Manager 2026-04-15 7.5 High
CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists that could cause a crash of the Accutech Manager when receiving a specially crafted request over port 2536/TCP.
CVE-2024-8518 1 Schneider-electric 1 Zelio Soft 2 2026-04-15 3.3 Low
CWE-20: Improper Input Validation vulnerability exists that could cause a crash of the Zelio Soft 2 application when a specially crafted project file is loaded by an application user.