Total
43 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2012-3032 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2026-04-29 | 7.5 HIGH | N/A |
| SQL injection vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to execute arbitrary SQL commands via a crafted SOAP message. | |||||
| CVE-2011-4879 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 8.5 HIGH | N/A |
| miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request. | |||||
| CVE-2011-4877 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 7.1 HIGH | N/A |
| HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cause a denial of service (application crash) by sending crafted data over TCP. | |||||
| CVE-2011-4514 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 10.0 HIGH | N/A |
| The TELNET daemon in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not perform authentication, which makes it easier for remote attackers to obtain access via a TCP session. | |||||
| CVE-2011-4878 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 7.8 HIGH | N/A |
| Directory traversal vulnerability in miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to read arbitrary files via a ..%5c (dot dot backslash) in a URI. | |||||
| CVE-2011-4512 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 5.0 MEDIUM | N/A |
| CRLF injection vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via unspecified vectors. | |||||
| CVE-2013-0678 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2026-04-29 | 4.0 MEDIUM | N/A |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. | |||||
| CVE-2013-3958 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2026-04-29 | 7.5 HIGH | N/A |
| The login implementation in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, has a hardcoded account, which makes it easier for remote attackers to obtain access via an unspecified request. | |||||
| CVE-2011-4510 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 4.3 MEDIUM | N/A |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511. | |||||
| CVE-2011-4513 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 10.0 HIGH | N/A |
| Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file, related to the HMI web server and runtime loader. | |||||
| CVE-2013-4911 | 1 Siemens | 1 Wincc | 2026-04-29 | 6.8 MEDIUM | N/A |
| Cross-site request forgery (CSRF) vulnerability in Siemens WinCC (TIA Portal) 11 and 12 before 12 SP1 allows remote attackers to hijack the authentication of unspecified victims by leveraging improper configuration of SIMATIC HMI panels by the WinCC product. | |||||
| CVE-2013-3957 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2026-04-29 | 7.5 HIGH | N/A |
| SQL injection vulnerability in the login screen in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, allows remote attackers to execute arbitrary SQL commands via unspecified vectors. | |||||
| CVE-2011-4875 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2026-04-29 | 9.3 HIGH | N/A |
| Stack-based buffer overflow in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to execute arbitrary code via vectors related to Unicode strings. | |||||
| CVE-2017-12069 | 2 Ocpfoundation, Siemens | 4 Local Discovery Server, Ua .net, Simatic Pcs7 and 1 more | 2025-04-20 | 6.4 MEDIUM | 8.2 HIGH |
| An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker. | |||||
| CVE-2014-4686 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 6.8 MEDIUM | N/A |
| The Project administration application in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, has a hardcoded encryption key, which allows remote attackers to obtain sensitive information by extracting this key from another product installation and then employing this key during the sniffing of network traffic on TCP port 1030. | |||||
| CVE-2014-4685 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 4.6 MEDIUM | N/A |
| Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows local users to gain privileges by leveraging weak system-object access control. | |||||
| CVE-2014-4683 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 4.9 MEDIUM | N/A |
| The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a (1) HTTP or (2) HTTPS request. | |||||
| CVE-2015-2823 | 1 Siemens | 6 Simatic Hmi Basic Panels Generation 1, Simatic Hmi Basic Panels Generation 2, Simatic Hmi Comfort Panels and 3 more | 2025-04-12 | 6.8 MEDIUM | N/A |
| Siemens SIMATIC HMI Basic Panels 2nd Generation before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Comfort Panels before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Advanced before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC WinCC Runtime Professional before WinCC (TIA Portal) 13 SP1 Upd2, SIMATIC HMI Basic Panels 1st Generation (WinCC TIA Portal), SIMATIC HMI Mobile Panel 277 (WinCC TIA Portal), SIMATIC HMI Multi Panels (WinCC TIA Portal), and SIMATIC WinCC 7.x before 7.3 Upd4 allow remote attackers to complete authentication by leveraging knowledge of a password hash without knowledge of the associated password. | |||||
| CVE-2014-4682 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 5.0 MEDIUM | N/A |
| The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request. | |||||
| CVE-2014-4684 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 6.0 MEDIUM | N/A |
| The database server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a request to TCP port 1433. | |||||