The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
References
Configurations
No configuration.
History
13 Mar 2026, 20:06
| Type | Values Removed | Values Added |
|---|---|---|
| Summary |
|
12 Mar 2026, 21:16
| Type | Values Removed | Values Added |
|---|---|---|
| New CVE |
Information
Published : 2026-03-12 21:16
Updated : 2026-03-13 20:06
NVD link : CVE-2026-3611
Mitre link : CVE-2026-3611
CVE.ORG link : CVE-2026-3611
JSON object : View
Products Affected
No product.
CWE
CWE-306
Missing Authentication for Critical Function